Solution
Energy saving transformation
1. overview:
In the central air conditioning system, the capacity of the chilled water pump and the cooling water pump is selected according to the maximum design heat load of the building, and there is a certain design margin. In the system that does not use speed regulation, the pump runs at full speed at power frequency all the year round, so it has to use throttling or backflow to adjust the flow, resulting in a large number of throttling or backflow losses, and for the pump motor, Because it runs at full speed at power frequency, it causes a great waste of energy. Due to the change of the four seasons, rain, rain, snow and day and night, the outside temperature is different, which makes the heat load of the central air conditioner far lower than the design load most of the time. That is to say, the central air conditioning is actually running at low load most of the time. According to statistics, 67% of the engineering design heat load value is 94-165W/m2, while in fact 83% of the engineering heat load is only 58-93W/m2, and the full load operation time does not exceed 10-20 hours per year. Practice has proved that in the central air conditioning circulation system (cooling pump and freezing pump) access to the frequency conversion system, the use of frequency conversion technology to change the motor speed to adjust the flow and pressure changes used to replace the valve control flow, can achieve significant energy saving effect.
2. energy saving principle:
According to the working principle of water pump and fan of fluid transmission equipment, the flow rate (air volume) of water pump and fan is proportional to its rotating speed. The pressure (lift) of water pump and fan is proportional to the square of its rotating speed, while the shaft power of water pump and fan is equal to the product of flow and pressure. Therefore, the shaft power of water pump and fan is proportional to the third power of its rotating speed (I .e. proportional to the third power of power of power of power supply frequency): reduce the speed of the water pump, fan, the power of the water pump, fan can be reduced more. For example, if the power supply frequency is reduced from 50Hz to 45Hz, P45/P50 =(45/50)3=0.729, I .e. P45 = 0.729P50(P is the motor shaft power); If the power supply frequency is reduced from 50Hz to 40Hz, P40/P50 =(40/50)3=0.512, I .e. P40 = 0.512P50(P is the motor shaft power).

As can be seen from the above, with the frequency converter for flow (air) control, can save a lot of energy. The central air conditioning system is designed according to the maximum cooling demand on site. Its cooling pump and freezing pump are considered according to the maximum working condition of a single equipment. In actual use, there are more than 90% of the time. The cooling pump and freezing pump all work under non-full load. The use of valves and automatic valve adjustment not only increases the throttling loss of the system, but also causes the entire air-conditioning system to work in a fluctuating state due to the phased adjustment of the air-conditioning system. The problem can be solved once and for all by installing a frequency converter on the cooling pump and the freezing pump, and automatic control can be realized, and the investment can be recovered through frequency conversion energy saving. At the same time, the soft start function of the frequency converter and the characteristics of smooth speed regulation can realize the smooth adjustment of the system, make the working state of the system stable, and extend the service life of the unit and the network management.

Therefore, the variable flow air conditioning water system, which changes the water volume with the thermal load, shows great advantages and is thus widely used. The frequency converter is used to adjust the pump speed, which can easily adjust the water flow. According to the feedback signal of the load change, the PID adjustment and the frequency converter form a closed-loop control system, so that the pump speed changes with the load, thus energy saving can be realized, and the energy saving rate is usually above 20%. The power saving rate of the transformation is closely related to the user's usage. Under normal circumstances, the power saving rate in spring and autumn is relatively high, reaching more than 40%. In summer, due to the large power required by the user itself, the space that can be saved is limited. Generally around 20%.
3. energy saving programme:
1. The existing central air conditioner in Renda Building is a set of units, with 2 15KW cooling pumps (one for use and one for standby) and 2 11W refrigeration pumps (one for use and one for standby). As there is not much room for renovation of the main compressor, we only carry out energy-saving renovation on the cooling system and refrigeration system.
During the actual operation of the central air conditioner, the temperature difference between the inlet and outlet of the cooling system and the refrigeration system (△T) is about 2 ℃, according:
Heat taken away by chilled water and cooling water (r)_= flow rate (Q)× temperature difference (△T)
We can appropriately increase the temperature difference (T), reduce the flow (Q), that is, reduce the speed, you can achieve the purpose of energy saving.
The principle diagram of frequency conversion transformation of central air conditioning system is as follows:

2. Chilled water system
For the chilled water system, because the temperature of the low-temperature chilled water depends on the operating parameters of the evaporator, the temperature difference can be controlled only by controlling the temperature of the high-temperature chilled water (backwater). Now a temperature sensor, a PID regulator and a frequency converter are used to form a closed-loop control system.
3. Cooling water system
For the cooling water system, the temperature of the cooling water on both sides of the condenser is taken as the control parameter, and a closed-loop control system is formed by temperature sensor, PID temperature regulator, frequency converter and cooling water pump. The cooling water temperature difference is controlled at △T2, so that the rotating speed of the cooling water pump changes according to the change of thermal load, while the temperature difference of the cooling water pump remains unchanged at the set value, so that the cooling water pump system can save the maximum energy.
4. Control mode
This scheme is installed on the basis of retaining the original power frequency system, adopts PLC to automatically switch the pump, and can monitor the power consumption time and condition. With the installation of electricity meter, the power saving situation can be clearly known, which is convenient to carry out contract energy management (EMC).
Performance of 4. central air conditioning system after frequency conversion:
(1) the use of inverter closed-loop control, according to the need for software configuration and set the temperature of PID adjustment, so that the motor output power with the change of thermal load changes, to meet the requirements of the use of the premise to achieve maximum energy saving.
(2) Due to the slow-down operation and soft start-up, vibration, noise and wear are reduced, the maintenance cycle and service life of the equipment are extended, the MTBF (mean time to failure) value of the equipment is improved, and the impact on the power grid is reduced. Improve the reliability of the system.
(3) The system has various protective measures, which greatly improves the operation rate and safety reliability of the system.
(4) The frequency conversion speed regulation closed-loop control system and the original power frequency control system are interlocked with each other, which does not affect the operation of the original system, and the original power frequency control system can still operate normally when the frequency conversion speed regulation closed-loop control system is overhauled or malfunctions.