Constant pressure water supply industry
Water supply system is an indispensable part of national production and life. The traditional water supply method covers a large area, the water quality is easy to be polluted, and the infrastructure investment is large. The main disadvantage is that the water pressure cannot be kept constant, which leads to energy waste. Variable frequency speed control technology is a new mature AC motor stepless speed control technology, which is widely used in the field of speed control, especially in the water supply industry, because of its unique and excellent control performance. Due to the special needs of safety production and water supply quality, there are strict requirements for constant pressure water supply pressure, so frequency conversion speed regulation technology has been more in-depth application. The constant pressure water supply method has advanced technology, constant water pressure, convenient operation, reliable operation, energy saving, and high degree of automation. At present, the industrial developed countries have widely adopted frequency conversion speed regulation technology, and it is also a new power-saving technology promoted by the state in my country. Inverter used in sugar industry fans, pumps, presses, centrifuges and other loads, can achieve significant energy saving effect.
1. working principle:
1. Working condition of original water supply system:
The company is a sugar factory. The original water supply system consists of a pipe network system. The water pump motor is 155KW and a starter. The water pump is cut by the upper and lower limits of pressure. The water pressure changes greatly with the change of production water consumption and the pump is cut. The pump unit cut-in has a great impact on the power grid. According to the requirements of the production process on water pressure and flow, the return valve needs to be opened for adjustment.
2. Frequency conversion energy-saving transformation scheme:
From the above system conditions, it can be seen that the system is suitable for frequency conversion and energy saving transformation, and the transformation scheme is as follows:
The system adopts frequency conversion control, pressure sensors are installed on the pipe network to detect the water pressure of the pipe network immediately. According to the change of production water consumption, the frequency conversion control system automatically adjusts the speed of the pump motor to control the water supply of the system and ensure the constant water pressure of the pipe network. The inverter is equipped with a starter to prevent the failure caused by the inverter and can be switched to the power frequency at any time. After the transformation, the power saving effect is obvious and the constant pressure water supply greatly improves the production process. The control diagram of the modified system is as follows:
2. System Configuration:
1. Constant pressure water supply function:
The AD300 frequency conversion system has a built-in PID, and the remote pressure gauge of the pipe network detects the pressure of the pipe network in real time and converts it into a 0~10V voltage signal, which is directly sent to the analog voltage input port of the frequency converter to set the given pressure value and PID parameter value. The frequency output is controlled after the built-in PID operation of the frequency converter. The system parameters can be adjusted in actual operation, so that the system control response is fast. The pressure of the pipe network can be arbitrarily given according to the production process, and the frequency conversion system automatically follows the control to keep the pressure set by the pipe network constant, which not only saves energy but also meets the water pressure requirements of sugar production.
2. Frequency conversion switching function:
Sugar industry water supply system reliability requirements are high, once the failure will affect the entire production has a serious impact, so the system set up a frequency conversion switching function. Under normal circumstances, the system runs in the state of frequency conversion and constant pressure water supply. When the frequency converter fails or is routinely overhauled, it can be switched to power frequency operation immediately, and the water pump is started with the original standby self-coupling step-down starting system, thus ensuring the continuity of water supply. The reliability of the whole system can well meet the requirements of production. The two sets of starting systems are electrically interlocked to prevent misoperation and ensure the safe operation of the system.
3. parameter settings:
F0.02 = 1 Operation control mode is external terminal
F0.03 = 7 frequency set to internal PID
F6.01 = 1 X1 terminal forward rotation operation
F6.03 = 8 RST reset
F7.03 = 16 Inverter fault output
F8.00 = 0 PID number given quantity selection (default)
F8.01 = 0 AI1 feedback quantity selection
F8.02 = XX analog PID digital given (according to the pressure setting)
4. after the transformation of income:
1, extend the service life of equipment and pipe network, reduce the workload of system maintenance.
Due to the use of frequency conversion constant pressure control, the start of the water pump is a soft start, which eliminates the impact of the impact torque on the motor when the large motor starts, and the impact of the water pump at the start is greatly reduced. At the same time, due to the soft start and the constant pressure control of the water pressure, The water hammer effect on the pipe network during startup is eliminated, and the pipe burst phenomenon no longer occurs. Therefore, the service life of the original equipment is prolonged, the failure rate is greatly reduced, and the workload of system maintenance is reduced.
Improve the quality of water supply and improve the reliability of the entire system.
After adopting the frequency conversion constant pressure control system, the water supply pressure can be adjusted very smoothly, and the staff on duty can adjust and control the system more stably and freely. With the change of the production process, the water supply pressure of the system can be easily adjusted. Due to the adoption of the new system, the failure rate is greatly reduced, and the two start-up systems can be used as standby for each other, ensuring the continuity of the system water supply and providing a reliable guarantee for the economic optimization of the system.
3, improve the power situation of the factory.
After adopting frequency conversion soft start, the impact of the original start-up system on the power grid is eliminated, the power factor of the new system can reach 0.95, the efficiency can reach 0.98, the working current of the system is greatly reduced, the line loss is also greatly reduced, and the power consumption of the factory is improved.
4. The energy saving effect is remarkable and the economic benefit is considerable.
In order to maintain the basic constant water pressure in the operation of the original system, in addition to the need to repeatedly switch the pump set, but also need to use the return valve for small-scale adjustment, the pump switch on the power grid impact but also need to consume electricity, return valve adjustment basically will not reduce the consumption of pump power. After frequency conversion is adopted, the variable frequency pump group can automatically adjust the rotation speed of the pump motor according to the water pressure required for production to keep the pressure of the pipe network constant. The variable frequency pump group can adjust the real-time range widely, the number of switching of the pump group is greatly reduced, and the energy saving effect of the system is remarkable. On average, the power saving rate of the whole system is about 30%, and the economic benefits are considerable.