Inclined shaft lifting under mine
Release time:
2020-09-10
1. overview:
Mine hoisting includes shaft hoisting and inclined shaft hoisting. Mine hoist is the key equipment of mine production, which is referred to as the "throat" of mine ". It is responsible for the mine ore, waste rock, equipment, materials, personnel and other lifting, decentralization tasks. It plays a very important role in mine production.
The inclined shaft hoist of a group company 3-2 ore body adopts the traditional AC speed regulation mode of rotor winding series resistance. The speed regulation mode has the following problems: first, the electromagnetic relay is used more, and the fault judgment and elimination time is long. After long-term operation, the failure rate is high, not only the repair cost is high, but also the ore output is affected. Second, the automation degree of lifting control is low, the noise during operation is large, the temperature of lifting machine room is high, the driver of lifting machine is easy to fatigue and the labor intensity is high. Third, when lifting heavy objects at continuous low speed, the resistance heats up seriously, often burns out the resistance connection line, and consumes large energy. Fourth, large mechanical impact on wire rope, reducer, etc.
2. transformation scheme and system composition:
1. Renovation scheme
The AC speed regulation system is composed of frequency conversion speed regulation device, programmable controller, energy feedback unit and touch screen, which replaces the original series resistance speed regulation system.
2. System composition
System composition principle block diagram, as shown in Figure 1:

The frequency conversion circuit includes a knife switch, a circuit breaker, a frequency converter, a contactor at the lower end of the frequency converter, and an energy feedback unit. The energy feedback unit constitutes a cabinet.
Control circuit: mainly by the main PLC control, auxiliary PLC control, touch screen, relay auxiliary control, console. Among them, the main PLC control and the auxiliary PLC control are each other's main and auxiliary, the relay auxiliary control, the main and auxiliary PLC control are installed in the same control cabinet, and the touch screen is installed on the operation table as the upper computer. Encoders are installed on the motor and drum as position and speed feedback signals. The speed encoder signal installed on the motor is fed back to the frequency converter to form PG vector control. Another encoder signal is fed back to the PLC for speed and position calculations. The speed measuring motor signal, oil temperature and oil pressure signal and other switching signals enter the PLC system.
3. working principle:
1. Functions of the system in four states: stop, manual, automatic and sliding:
Stop: in this state, the system stops working, all operations cannot be carried out, and the winch is in the brake shoe braking state;
Manual: in this state, when the system meets the premise of safe operation, according to the instrument and the parameters displayed on the touch screen, through the master controller to the winch upward, downward normal manual operation.
Automatic: in this state, the uplink and downlink buttons will automatically complete the whole process of uplink and downlink. When the line is halfway, it can be stopped by manual intervention through the stop button, and can be started again through the uplink and downlink buttons.
Sliding down: when the system fails to perform normal upward and downward operations due to serious faults, the function switch shall be switched to this position, and the winch shall be slid down to the determined position through the master controller.
Through the double PLC digital control technology, the winch double-wire protection and control stipulated in the "Coal Mine Safety Regulations" is realized. Winch double-wire system protection and control has the following characteristics:
(1) High speed control accuracy, wide speed range, speed control accuracy of not less than 0.05%.
(2) Two-wire protection: A hardware safety circuit and two software safety circuits are redundant with each other, making the system safer and more reliable.
(3) Two-wire control: During normal operation, due to the use of dual PLC systems to monitor each other, mutual redundancy. When one of the PLC system fails, the other PLC system can still be put into emergency start-up, which improves the operation reliability of the winch system.
2. Protection and chain function:
2.1. During safety braking, cooperate with the safety valve of the hydraulic station to make the hoist realize primary or secondary braking, and at the same time, the frequency converter enters the feedback braking state.
2.2. In any case, only the driver can make the hoist run after receiving the driving signal.
2.3. When the lubricating oil pressure is too high or too low, the lubricating oil filter or the oil filter of the hydraulic station is blocked or the oil temperature is high during the lifting process, the corresponding fault information is displayed on the touch screen, and the corresponding information light is lit to inform The driver can complete this lifting work, and the driver is allowed to carry out the next lifting work after the fault is removed.
2.4. When the hoist stops in the middle due to failure and the lifting container is located in the deceleration section stroke, the driver is allowed to choose to drive according to the last driving direction after troubleshooting, and can only drive at low speed: if the lifting container is not in the deceleration stroke, the wellhead will send a start signal to allow the driver to drive at high speed.
2.5, the whole mine power failure, by the PLC system to ensure that the hoist can achieve secondary braking, and do a good job of hoist backup protection.
2.6. The working braking torque of the disc brake is adjustable. Emergency braking (safety braking) can produce secondary braking to avoid mechanical impact.
3. Stroke control function:
Stroke control is completed by the PLC system, the main hoist lifting process is divided into different lifting speed requirements of the stroke interval. According to the actual situation of each stroke interval and different speed requirements, the speed of the inverter is changed to a given value, and a closed loop is formed to smoothly adjust the lifting speed of the hoist: the stroke control not only controls the speed of the entire lifting stroke process of the hoist, but also controls the parking and braking process of the hoist. Stroke control can well prevent the occurrence of accidents such as over-rolling, over-releasing, derailment and rollover of the hoist, and is especially suitable for special inclined shafts with bends and forks.
4. Brake control function:
The normal braking of the hoist includes feedback braking, brake braking and other methods. The realization of feedback braking is to introduce the inverter link in the DC link of the AC-to-AC voltage inverter. When the actual operating speed of the hoist is higher than the given operating speed, the motor is equivalent to a generator, and the DC link voltage increases to provide energy to the inverter and feed back to the grid, and the motor automatically runs in the braking state. In order to achieve the purpose of accurate parking of the inverter, it is good to prevent mechanical impact and rapid decline. The brake is generally used when parking. When running to the parking space, the stroke controller sends a parking signal to the frequency converter, and at the same time, it sends a brake control signal to the brake to implement the brake. In case of derailment and other accidents, the operation control shall implement emergency brake.
This system adopts the regenerative braking method, in the braking process, the hoist runs smoothly, and the braking energy is fed back to the network, which has a certain energy-saving effect. 6920V braking sequence, as shown below:

5. Main device functions:
5.1, programmable controller function.
All control of the system except emergency protection function is completed by programmable controller ((PLC. The programmable controller configured by the system can adapt to harsh industrial environment and has strong anti-interference ability. It has two communication ports (programmer port and universal port) that can be used at the same time. Through communication with the LCD touch screen, it can intuitively and conveniently display the system operation state, fault state, operation parameters, the state of all switching elements and various fault and alarm information; receive the signals from the voltage transmitter, current transmitter and encoder of the system configuration, and control, monitor and protect the winch after operation and processing. During emergency braking (safety braking), the programmable controller controls the disc brake to generate secondary braking to avoid mechanical impact. Simplify the system programmable controller control flow chart, as shown in Figure 2.
5.2, inverter function
The inverter receives the speed feedback signal from the rotary encoder and forms PG vector control to realize the stepless speed regulation of the motor. This system is equipped with 6920V series frequency converter and energy feedback unit:
1) Integrated scheme: the organic combination of motor drive and lifting logic control is adopted to eliminate the PLC in the original system, reduce potential failure points, simplify system wiring, simple and flexible debugging, and represent the development direction of crane control in the future;
2), wide voltage design can better meet the harsh power environment
3), crane professional logic design: set many years of experience in crane industry design, design expert, widely used lifting mechanism control and safety logic, including timing coordination, anti-slip hook, and other functions, to provide perfect solutions for supporting customers;
4), in the mining, metallurgy, road construction industry feeding system has a special fixed length design, so that the control is more safe and reliable. Accurate torque control: stall prevention function, fault reset and retry function; The addition of a rotary encoder can realize full frequency domain magnetic flux current vector control, keeping the motor at 150% output torque at 0.5Hz.
Main technical parameters of frequency conversion device:
(1), the input power supply voltage AC304-456V, frequency 50HZ; Voltage allowable fluctuation range/-20%; Frequency allowable fluctuation range 48-65HZ;
(2), the output frequency range of 0~50Hz continuously adjustable;
(3) Rated heavy-duty output power: 160kW.
(4) Overload capacity 150, 1 minute; 180, 20s
(5), a higher power factor cos φ>0.98;
(6) When running at low frequency, it has automatic torque lifting function and slip compensation function to ensure 150% of the rated torque;
(7) The frequency converter is equipped with protections such as overvoltage, undervoltage, overcurrent, overload, overheating of power components and lack of phase of the motor, and is equipped with fault memory function, which can retain the functional numbers of the last 3 faults and the parameters of the last fault;
(8), total harmonic content THD<5%.
Main technical principles:
(1) The use of all-digital speed sensor closed-loop vector control, so that the system has a wide speed range and high speed control accuracy. Frequency converter in low frequency operation, but also to ensure that more than 150% of the rated torque output. The maximum torque is twice the rated torque. The basic principle of vector control is to measure and control the stator current vector of the asynchronous motor, and control the excitation current and torque current of the asynchronous motor according to the principle of field orientation, so as to control the asynchronous motor. The purpose of motor torque. Specifically, the stator current vector of the asynchronous motor is decomposed into the current component that generates the magnetic field (excitation current) and the current component that generates the torque (torque current) to be controlled separately, and the amplitude and phase of the two components are controlled at the same time. Stator current vector, this control method is called vector control method. In this way, a three-phase asynchronous motor can be equivalent to a DC motor to control, thus obtaining the same static and dynamic performance as the DC speed control system.
PLC control process, as shown in Figure 2:

5.3. Energy feedback unit
The main function is to improve the braking ability of the frequency converter, and the braking energy of the weight under the winch is fed back to the power grid to achieve the purpose of energy saving.
Main functions of 5.4 and console
The console is equipped with a manually operated master controller. Manual adjustment of braking force and winch speed. And equipped with manual and foot emergency brake switches, fast braking when an emergency occurs
5.5, LCD touch screen function
Through communication with the programmable controller, the system operation state, fault state and operation parameters' such as winch operation speed, lifting container position, motor current and voltage, etc.) can be visually displayed, and the state of all switching elements and various faults and alarm times can be displayed. The programmable controller can be modified to change the internal parameter settings (corresponding right is required: the operator password can be set and modified according to the permission with password protection function. Operators with different security levels have different operating rights
4. System Configuration:
1. Selection of frequency converter
The motor driven by the inverter is: JR 127- 8 115k W
Rated voltage: 380V
Fixed current: 227A
According to the principle that the rated output current of the frequency converter is greater than or equal to the fixed current of the motor number × 1.1
227 × 1.1 = 249.7A
Check the sample of AD300 series inverter:
Capacity 132kVA rated output current: 250A
Capacity 160k VA rated output current: 300A
Considering the environment and transportation conditions under the pit, the final choice of inverter capacity is I 60kVA.
2, programmable controller selection.
Comprehensive consideration of over-rolling, over-rolling, manual upward, manual downward, automatic upward, automatic downward, normal shutdown, emergency shutdown, safety circuit, hydraulic station control, disc brake control, various working indicator lights, report indicator lights, etc. And the interlocking control between the various operating conditions. And consider some redundancy.
3. Selection of energy feedback unit
3.1. Brake voltage selection
Brake voltage selection is too low. When the grid voltage rises, it will cause the brake unit to malfunction. However, if the braking voltage is selected too high, it will pose a threat to the safe operation of the equipment. For 380V system, the braking voltage is generally 700V.
3.2. Brake current selection
The braking current refers to the DC current flowing through the braking resistor and the braking unit during braking.
Selection basis: the brake must fully absorb the regenerative energy of the motor
Braking absorption power (U×I)= motor regenerative energy (W) = 1000 ×P×η
P ____ Rated power of motor (kW)
U ____ DC operating point of brake unit, usually 700V
I ____ Braking current (A)
η ____ The conversion efficiency of mechanical energy during feedback, usually η = 0.7
Calculated: I = 115
3.3, power selection
Motor regeneration must be absorbed and fed back to the grid
PR=P×Kf×η×e
PR ---- feedback unit power (Kw)
η ____ The conversion efficiency of mechanical energy during feedback, usually η = 0.7
Safety factor of braking power consumption ε. Take ε = 1.4
Kf ____ braking frequency, which refers to the proportion of the regeneration process in the working time of the whole motor.
Check relevant data Kf take 60%
Calculated PR = 67.62 kW
Selected feedback unit power 70 kW
The application of variable frequency speed regulation system in underground hoist system can solve the problems of speed regulation and start-up, realize soft start and soft stop, reduce mechanical impact and make operation more stable and reliable. The impact current is very small when starting and accelerating gear shifting, which reduces the impact on the power grid, simplifies the operation and reduces the labor intensity of workers. The running speed curve is S-shaped, which makes acceleration and deceleration smooth and has no impact feeling; safety protection function is complete. In addition to the general overvoltage, undervoltage, overload, short circuit, temperature rise and other protection, there are also interlocking protection, automatic speed limit protection and so on. The promotion of frequency conversion speed regulation system instead of series resistance speed regulation system in the pit under inclined and winch is to improve the technical content of mine pit under inclined shaft winch and open up a new way to save energy and tap potential.
Previous
Next
Previous
Next
Latest information
The role of the inverter in the four aspects of industry
The energy saving level of frequency converter is mainly reflected in the application of fan and centrifugal pump. After selecting the wind turbine and pump load, the energy saving rate is 20%-60% due to the ratio of the specific cost of the wind turbine and the pump load and the three-square speed ratio.
2020-07-29
What are the differences between frequency converter and soft starter
The frequency converter is a power output control system that uses the principle of inverter and electronic information technology to control the communication motor according to the frequency change of the switching power supply.
2020-07-29
11KW-15KW plastic shell inverter research and development completed, small batch trial production!
11KW-15KW plastic shell inverter research and development completed, small batch trial production!
2020-07-29